SKU: RGBM505LN
Technical Data
Technical Data | Value | Unit |
---|---|---|
Heat Rated Output | 700-5100 / 602-4388 | (kW) / (Mcal/h) |
NOx Class | III | — |
Turn Down Ratio | 1:7 | — |
G20 Gas Rated Output | 700-5100 | kW |
G20 Gas Flow Rate | 70-510 | m3/h |
G25 Gas Rated Output | 700-5100 | kW |
G25 Gas Flow Rate | 81-593 | m3/h |
LPG Rated Output | 750-5100 | kW |
LPG Gas Flow Rate | 29-198 | m3/h |
Light Oil Rated Output | — | kW |
Light Oil Flow Rate | — | kg/h |
Heavy Oil Rated Output | — | kW |
Heavy Oil Flow Rate | — | kg/h |
Gas Line Pressure (Low pressure) | 146-360 | mbar |
Gas Line Pressure (High Pressure type) | 1.5-4 | bar |
Input Gas Pipe Size (Low Pressure) | DN 80 | — |
Input Gas Pipe Size (High Pressure) | DN 80 | — |
Electric Power Supply Phase | 3 | ph |
Electric Power Supply Frequency | 50 | Hz |
Electric Power Supply Voltage | 380-400 | V |
Fan Electrical Motor Power | 11 | kW |
Fan Motor Speed | 2900 | rpm |
Pump Model | — | — |
Pump Motor Power | — | kW |
Pump Motor Speed | — | rpm |
Gas Operation Mode | Electrical Modular | Lamtec |
Oil Operation Mode | — | Lamtec |
Centrifugal Fan | 363x103x42 | mm |
IP (With reference to ISIRI 2868) | 43 | — |
Total Dimension | 1720x925x800 | mm |
Weight | 221 | Kg |